| Paramètre | Valeur |
|---|---|
| Article | Specifications |
| Poids net | 80 g approx. |
| Type de sortie | Line driver |
| Numéro de pièce | AFP0HPG02L |
| Nom du produit | FP0H positioning units |
| Temps de démarrage | 0.02 ms or 0.005 ms selectable (Note)Note : The startup time can be changed by the control code setting in the shared memory. The factory setting (default setting) is 0.02 ms. The startup time is the time from the start request to the first pulse output. |
| Mode de fonctionnement | E point control (Linear accelerations / decelerations, S accelerations / decelerations)P point control (Linear accelerations / decelerations, S accelerations / decelerations)Home return function (Home search)JOG operation function (Note 1)JOG positioning functionPulser input function (Note 2)• Transfer multiplication ratio (× 1, × 2, × 5, × 10, × 50, × 100, × 500, × 1000)Real-time frequency change functionInfinity output functionNote1 : When selected linear acceleration / deceleration operation, the target speed can be changed during an operation.Note2 : Pulser input function and feedback counter function use the same pulse input terminal, so the both cannot function simultaneously. |
| Numéro de produit | AFP0HPG02L |
| Autres fonctions | The flag to compare the elapsed value is built in. (The timing signal outputs at the optional position during an operation.) |
| Nombre d'axes contrôlés | 2 axes, independent |
| Nombre de points occupés | Input 32 points, Output 32 points |
| Retour à la source : Signal d'entrée | Home input, Near home input, Over limit input (+), Over limit input (-) |
| Retour à la source : Signal de sortie | Deviation counter clear signal |
| Commande de vitesse : Plage de commande | 1 pps to 4 Mpps(can set in 1 pps.) |
| Interface de sortie : Mode de sortie | 1 pulse output (Pulse and Sign), 2-pulse output (CW and CCW) |
| Alimentation externe : Tension | 21.6 to 26.4 V DC |
| Retour à domicile : Vitesse de retour à domicile | Speed setting possible (changes return speed and search speed) |
| Commande de position : Unités de commandement | Pulse unit (The program specifies whether Increment or Absolute is used.) |
| Commande de position : Nombre d'impulsions max. | Signed 32 bits (-2,147,483,648 to +2,147,483,647 pulses) |
| Fonction de compteur de retour d'information : Mode d'entrée | Two-phase input, Direction distinction input, Individual input (transfer multiple available for each.)Note : Pulser input function and feedback counter function use the same pulse input terminal, so the both cannot function simultaneously. |
| Alimentation externe : Consommation de courant | 30 mA |
| Fonction de compteur de retour d'information : Plage de comptage | Signed 32 bits (-2,147,483,648 to +2,147,483,647 pulses)Note : Pulser input function and feedback counter function use the same pulse input terminal, so the both cannot function simultaneously. |
| Commande d'accélération/décélération : type courbe en S | Can select from Sin curve, Secondary curve, Cycloid curve and Third curve. |
| Commande d'accélération/décélération : Temps d'accélération/décélération | 0 to 32,767 ms (can set in 1 ms) |
| Commande d'accélération/décélération : Méthode d'accélération/décélération | Linear acceleration / deceleration, S acceleration / deceleration |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation