| Paramètre | Valeur |
|---|---|
| For DC see load limit curve, e.g., the following values: | |
| Taper | block modular |
| Profondeur | 54 mm |
| Largeur | 53.6 mm |
| Hauteur | 126.1 mm |
| Consommation de courant | max. 280 mA (all relays pick up) |
| Type de produit | I/O component |
| Type de montage | DIN rail mounting |
| Famille de produits | Axioline F |
| Tension d'alimentation | 5 V DC (via bus base module) |
| Nom de la connexion | Axioline F connector |
| Révision de l'article | 02 |
| Degré de pollution | 2 |
| longueur de dénudage | 8 mm |
| Méthode de connexion | Bus base module |
| Position de montage | any (observe temperature and current derating) |
| Nombre de sorties | 4 (floating) |
| Étendue de la prestation | including bus base module and Axioline F connectors |
| Courant de commutation | max. 8 A AC (cos phi = 1) |
| Zone d'adresse de saisie | 0 Byte |
| Note sur les dimensions | The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715). |
| Capacité de commutation | max. 2000 VA |
| vitesse de transmission | 100 Mbps |
| Dessin coté | |
| Note sur l'application | Only for industrial use |
| Zone d'adresse de sortie | 1 Byte |
| Fréquence de commutation | max. 6 (per minute) |
| Degré de protection | IP20 |
| Nombre d'interfaces | 2 |
| Catégorie de surtension | III (EN 61010-2-201/UL 61010-2-201), up to 2000 m above sea levelII (EN 61010-2-201/UL 61010-2-201), up to 3000 m above sea level |
| Désignation standard | Ambient conditions |
| Technologie de connexion | 2-conductor |
| type de commutation de contact | N/O contact |
| durée de vie mécanique | 10x 106cycles |
| Données des paramètres requis | 1 Byte |
| Pression d'air (fonctionnement) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Normes/spécifications | IEC 61850-3 |
| Section transversale du conducteur AWG | 24 ... 16 |
| Données de configuration requises | 6 Byte |
| Section transversale du conducteur rigide | 0.2 mm² ... 1.5 mm² |
| Note sur la méthode de connexion | Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.When selecting the cables, please note that in the case of a small conductor cross section and high current, the terminal point temperature may be up to 30 K above the ambient temperature. |
| Section transversale du conducteur, rigide | 0.2 mm² ... 1.5 mm² |
| Température ambiante (fonctionnement) | -25 °C ... 60 °C (max. 6 A/channel for wall mounting on horizontal DIN rail; max. 4 A/channel for any mounting position) |
| Pression d'air (stockage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Section transversale du conducteur flexible | 0.2 mm² ... 1.5 mm² |
| Humidité admissible (fonctionnement) | 5 % ... 95 % (non-condensing) |
| Section transversale du conducteur, flexible | 0.2 mm² ... 1.5 mm² |
| Tension d'essai : Contact/logique du relais | 4 kV |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Humidité admissible (stockage/transport) | 5 % ... 95 % (non-condensing) |
| Dissipation de puissance maximale en condition nominale | 1.4 W |
| Tension d'essai : Contact du relais / masse fonctionnelle | 4 kV |
| Capacité de commutation conforme à la norme IEC 60947-5-1 | 6 A (120 V (AC15)) |
| Tension d'essai : Contact de relais/contact de relais (contact ouvert) | 1 kV, 50 Hz, 1 min. |
| Tension d'essai : contact de relais/contact de relais (connecteurs mâles adjacents) | 2.5 kV |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation