| Paramètre | Valeur |
|---|---|
| Poids | 44 Kg |
| Bruit (dB) | 65 |
| Courant (A) | 5,5 |
| Tension (V) | 230-1-50/60 |
| Capacité (W) | 2000 |
| Caractéristiques | |
| (Données techniques) | EAC |
| Finition : (Données techniques) | RAL 7035. |
| Matériau : (Données techniques) | Galvanized steel powder coated / Stainless steel AISI 304L. Stainless steel AISI 316L available on request. |
| Homologations : (Données techniques) | CE, GOST. |
| Description : (Données techniques) | High performance cooling unit for vertical installation. CUO is the air conditioning solution for critical electronic environments including cabinets, shelters, cabins and many other demanding applications in which the air conditioner is installed outdoors. The unit is mounted flush with the outside surface, so maximizing space inside the enclosure. Common to all models is the self cleaning condenser coil which eliminates the necessity for an air filter, avoiding ordinary maintenance. The mechanical thermostat is inside the unit and it is adjustable between 25ºC and 45ºC, factory setting 35ºC.Cooling capacity shown in the table is at L35/L35, the cooling capacity for specific conditions are indicated in the diagrams. Ozone friendly refrigerant R134a. |
| Degré de protection : (Données techniques) | IP 54. |
| Type de connexion : (Données techniques) | Spring-type terminal included. |
| Limites de température intérieure : (Données techniques) | 25ºC to 45ºC. |
| Limites de température extérieure : (Données techniques) | -20ºC to 55ºC. |
Spécifications techniques et données de performance