| Paramètre | Valeur |
|---|---|
| 570 mA (IIB) | |
| EN | EN 61326, EN 60068-2-27, EN 60068-2-6 |
| NE | NE21 |
| ATEX | Sira 13ATEX4149X; II 3G Ex nA [ic] IIC T4 Gc |
| Couleur | green |
| Profondeur | 70.4 mm |
| IECEx | IECEx SIR 13.0060X; Ex nA [ic] IIC T4 Gc |
| Largeur | 17.7 mm |
| Hauteur | 93.9 mm |
| Signal | PROFIBUS |
| Note CCCex | Use in potentially explosive areas is not permitted in China. |
| Conformité | IEC 61158-2 |
| Type de produit | Device coupler |
| Inductance Li | 10 µH |
| Type de montage | DIN rail mounting |
| Capacité Ci | 0 µF |
| CSA, États-Unis/Canada | Class I, Div. 2, Groups A,B,C,D; Ex nA nL IIC T4 GcClass I, Zone 2, AEx nA nC IIC T4 Gc |
| Courant d'entrée Ii | 274 mA (IIC) |
| Tension d'entrée Ui | 32 V DC |
| Méthode de connexion | Pluggable screw connection with test points |
| Position de montage | Any orientation on DIN rail, NS 35, in acc. with EN 60715 |
| Dessin coté | |
| Fondation Fieldbus | FF-830 |
| Degré de protection | IP20 |
| Plage de tension d'alimentation | 9 V DC ... 32 V DC |
| Normes/réglementations | Ring wave noise immunity in acc. with IEC 61000-4-12 |
| Consommation de courant maximale | 29 mA |
| Consommation de courant typique | 27 mA |
| Température ambiante (fonctionnement) | -40 °C ... 85 °C |
| Conductor cross section AWG max. | 12 |
| Conductor cross section AWG min. | 24 |
| Section transversale du conducteur, rigide max. | 2.5 mm² |
| Section transversale du conducteur, rigide min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Indice d'inflammabilité selon la norme UL 94 | V0 |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Humidité relative maximale admissible (en fonctionnement) | 95 % (non-condensing) |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation