| Paramètre | Valeur |
|---|---|
| 235.18 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%) | |
| CEM | B |
| MTTF | 494.02 Years (SN 29500 standard, temperature 25°C, operating cycle 21%) |
| Note | UL 60079-0 Ed. 6 / UL 60079-7 Ed. 5, CSA 22.2 No. 60079-0 Ed. 3 / CSA C22.2 No. 60079-7 Ed. 2 |
| Taper | Book type |
| Profondeur | 119 mm |
| Largeur | 45 mm |
| Hauteur | 130 mm |
| Général | Support by phone or on-site (fee is charged) |
| Humidité | B |
| Enceinte | Required protection according to the Rules shall be provided upon installation on board |
| Vibration | A |
| Gestion | Web-based management (HTTP/HTTPS) |
| Redondance | MRP (Media Redundancy Protocol) |
| Certificat | DEMKO 16 ATEX 1709X |
| Nom de sortie | Alarm output |
| LED de signalisation | Data receive, link status |
| Température | B |
| Type de produit | Switch |
| Délai de signal | ≥ 6.5 µs (Store and Forward mode, 10/100 Mbps, depending on the frame size) |
| Section de test | 24 V supply / functional ground 500 V DC 1 min. |
| Type de montage | DIN rail mounting |
| Sécurité portuaire | MAC-based, RADIUS (IEEE 802.1X), MAC Authentication Bypass |
| Identification | II 3 G Ex ec IIC T4 Gc |
| Émission de bruit | EN 61000-6-4 |
| Immunité au bruit | EN 61000-6-2 |
| Famille de produits | Managed Switch 2000 |
| Affichage de l'état | LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed) |
| Fonctions de base | Store-and-forward switch, complies with IEEE 802.3 |
| Nombre de canaux | 8 (RJ45 ports) |
| Ondulation résiduelle | 3.6 VPP(within the permitted voltage range) |
| Révision de l'article | 08 |
| Fonctions de filtrage | Quality of Service (8 priority classes) |
| Matériau du boîtier | Polycarbonate fiber reinforced |
| Classe de protection | III (VDE 0106) |
| longueur de dénudage | 9 mm |
| Méthode de connexion | RJ45 |
| Diagnostic local | US1/2 Supply voltage US1, US2 Green LED |
| Tableau des adresses MAC | 8k |
| Choc (opération) | 30g (EN 60068-2-27) |
| propriétés spéciales | Extended temperature range |
| vitesse de transmission | 10/100 Mbps |
| Consommation de courant | 190 mA |
| Degré de pollution | 2 |
| Dessin coté | |
| Paramétrage IP | DHCP client |
| Note sur l'application | Only for industrial use |
| Tension d'alimentation (CC) | 24 V DC (redundant) |
| longueur de transmission | 100 m (per segment) |
| milieu de transmission | Copper |
| Fonctions supplémentaires | Transmission of MMS and GOOSE (IEC 61850-8-1) |
| Degré de protection | IP20 |
| Fonctions de diagnostic | RMON History |
| Plage de tension d'alimentation | 12 V DC ... 57 V DC |
| Synchronisation temporelle | SNTP (Simple Network Time Protocol) |
| Physique de la transmission | Copper |
| Approbation de construction navale | Tested in accordance with IEC 60945 and IACS E10 |
| Vibration (fonctionnement) | in acc. with IEC 60068-2-6: 5g, 150 Hz |
| Connexion d'alimentation | via COMBICON, max. conductor cross section 1.5 mm² |
| Références aux normes | EN 60079-0 |
| Pression d'air (fonctionnement) | 80 kPa ... 110 kPa up to 2000 m above mean sea level (Without derating) |
| Consommation de courant maximale | 1.3 A (US= Min, Tamb= Max, DOI= Max) |
| Fonctionnement du périphérique PROFINET | PROFINET device |
| classe de conformité PROFINET | Conformance-Class B |
| Section transversale du conducteur AWG | 24 ... 16 |
| Consommation de courant typique | 185 mA (at US= 24 V DC and 25 °C ambient temperature) |
| Compatibilité électromagnétique | Conformance with EMC Directive 2014/30/EU |
| Note sur la méthode de connexion | Auto negotiation and autocrossing |
| Section transversale du conducteur, rigide | 0.25 mm² ... 1.5 mm² |
| tension de commande du contact de signal | typ. 24 V DC |
| Température ambiante (fonctionnement) | -40 °C ... 70 °C |
| Conformité aux directives CEM | EN 61000-6-2 EN 61000-4-2 (ESD) Criterion B |
| Pression d'air (stockage/transport) | 79 kPa ... 108 kPa up to 2000 m above mean sea level (Without derating) |
| Humidité admissible (fonctionnement) | 10 % ... 95 % (non-condensing) |
| Indicateurs d'état et de diagnostic | LEDs: US1, US2 (power supply), Fail (alarm contact), 2 LEDs per Ethernet port (Link/Activity and Speed) |
| Section transversale du conducteur, flexible | 0.25 mm² ... 1.5 mm² |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Humidité admissible (stockage/transport) | 10 % ... 95 % (non-condensing) |
| Dissipation de puissance maximale en condition nominale | 4.95 W (US= Min, Tamb= Max, DOI= Max) |
| Exempt de substances susceptibles de nuire à l'application du revêtement | Yes |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation