| Paramètre | Valeur |
|---|---|
| GTIN | 4017918129675 |
| Note | Made to Order (non-returnable) |
| Clé de commande | 1677050 |
| page du catalogue | Page 515 (C-2-2017) |
| Unité d'emballage | 10 pc |
| Pays d'origine | DE (Germany) |
| numéro de tarif douanier | 85366990 |
| (Données commerciales clés) | Connectors may be operated only when there is no load/voltage. |
| Size (Key Commercial Data) | D25 |
| (Normes et réglementations) | No hazardous substances above threshold values |
| (Electrical characteristics) | IEC 60352 |
| Rated current (Material data) | 16 A |
| Tension de surtension nominale (Données sur les matériaux) | 4 kV |
| Poids par pièce (emballage exclu) | 45.640 g |
| Matériau de contact (conditions ambiantes) | Copper alloy |
| Tension nominale (III/3) (Données sur les matériaux) | 250 V |
| Normes et réglementations RoHS en Chine | Environmentally friendly use period: unlimited = EFUP-e |
| Méthode de connexion (Données commerciales clés) | Crimp connection |
| Contact numbering (Key Commercial Data) | 17 - 32 |
| Température ambiante (fonctionnement) (Général) | -40 °C ... 125 °C (including heating up of contacts) |
| Degree of pollution (Key Commercial Data) | 3 |
| Nombre de postes (Données commerciales clés) | 16+PE |
| Overvoltage category (Key Commercial Data) | III |
| Assembly instructions (Key Commercial Data) | To ensure correct use, installation in housing with IP54 protection or better is required |
| Conductor cross section (Key Commercial Data) | 0.14 mm² ... 4 mm² (applies to stranded conductors) |
| Matériau support de contact (conditions ambiantes) | PA |
| Matériau de la surface de contact (conditions ambiantes) | Ag (alternatively Au) |
| Insertion/withdrawal cycles (Key Commercial Data) | ≥ 500 |
| Connection cross section AWG (Key Commercial Data) | 20 ... 12 |
| Connection in acc. with standard (Electrical characteristics) | CSA |
| Longueur de dénudage du fil individuel (Données commerciales clés) | 8 mm |
| Constructional and testing regulations (Electrical characteristics) | DIN VDE 0627/86 |
| Flammability rating according to UL 94 (Electrical characteristics) | V0 |
Spécifications techniques et données de performance