| Paramètre | Valeur |
|---|---|
| -40 °F ... 158 °F (>131°F derating) | |
| MTTF | 778 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) |
| Profondeur | 114.5 mm |
| IECEx | Ex nA nC IIC T4 Gc |
| Gamme | ± 5 km (The range may be considerably above or below that stated, and depends on the environment, antenna technology, and the product used) |
| Choc | 16g, 11 ms |
| Largeur | 17.5 mm |
| Hauteur | 99 mm |
| Altitude | 2000 m |
| Sécurité | 128-bit data encryption |
| débit de données | 16 kbps (adjustable) |
| Direction | Bi-directional |
| Fréquence | 2400 MHz |
| Conformité | CE compliance (R&TTE directive 1999/5/EC) |
| Désignation | Wireless module |
| Note d'exportation | *The range may be considerably above or below that stated. It is dependent on the environment, antenna technology, transmission power, and the product used. |
| Interface 1 | RS-232 |
| Interface 2 | RS-485 |
| Interface 3 | Configuration interface |
| Type de contact | PDT |
| Filetage | M3 |
| Mode de données E/S | ≤ 99 (I/O extension modules per wireless network, serial interfaces deactivated) |
| Mode de fonctionnement | I/O data (Default setting, configuration via thumbwheel) |
| Affichage de l'état | Green LED (supply voltage, PWR) |
| Gamme de fréquences | 2.4002 GHz ... 2.4785 GHz |
| Distance du canal | 1.3 MHz |
| Matériel de contact | PdRu, gold-plated |
| Matériau du boîtier | PA 6.6-FR |
| Degré de pollution | 2 |
| Mode de données série | 0 (no I/O extension modules can be used) |
| longueur de dénudage | 7 mm |
| UL, États-Unis / Canada | UL 508 Listed |
| Méthode de connexion | COMBICON plug-in screw terminal block |
| Nombre de sorties | 1 |
| Couple de serrage | 0.6 Nm |
| Licences sans fil | Australia |
| connexion d'antenne | RSMA (female) |
| vitesse de transmission | 0,3 ... 115,2 kbit/s |
| Mode PLC/Modbus RTU | ≤ 99 (I/O extension modules per wireless network, access to extension modules via Modbus RTU protocol) |
| longueur de transmission | ≤ 15 m |
| Degré de protection | IP20 |
| Catégorie de surtension | II |
| Sensibilité du récepteur | -106 dBm (16 kbps) |
| Désignation standard | Ex Directive (ATEX) |
| Plage de tension d'alimentation | 19.2 V DC ... 30.5 V DC |
| résistance de terminaison | 390 Ω (switchable via DIP switches) |
| Instructions de montage | on standard DIN rail NS 35 in accordance with EN 60715 |
| Normes/réglementations | EN 60079-0 |
| Vibration (fonctionnement) | in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
| Signal de sortie de tension | 0 V ... 3 V |
| courant de commutation max. | 500 mA (30 V AC/DC) |
| Durée de vie électrique | 5 x 105cycles with 0.5 A @ 30 V DC |
| Consommation de courant maximale | ≤ 65 mA (@ 24 V DC, @ 25°C, stand-alone) |
| Nombre de groupes de canaux | 8 |
| Tension de commutation maximale | 30 V AC/DC |
| Protection contre les surtensions transitoires | Yes |
| Capacité de transmission maximale | ≤ 20 dBm (Outside of Europe, adjustable via software) |
| Capacité de transmission minimale | 0 dBm |
| Nombre d'appareils pris en charge | ≤ 250 (Addressing via PSI-CONF software) |
| Nombre de canaux par groupe | 55 |
| Température ambiante (fonctionnement) | -40 °C ... 70 °C (>55°C derating) |
| Conductor cross section AWG max. | 14 |
| Conductor cross section AWG min. | 24 |
| Humidité admissible (fonctionnement) | 20 % ... 85 % |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Nombre de modules d'extension possibles | ≤ 32 (per wireless module) |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Indice d'inflammabilité selon la norme UL 94 | V0 |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Humidité admissible (stockage/transport) | 20 % ... 85 % |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation