| Paramètre | Valeur |
|---|---|
| 230 V AC | |
| Note | Class B |
| Couleur | green |
| Profondeur | 43 mm |
| Saisir | asymmetrical 4 kV (Test Level 4) |
| Largeur | 72 mm |
| rigide | 0.2 mm² ... 2.5 mm² |
| Hauteur | 90 mm |
| Sortir | asymmetrical 2 kV (Test Level 3) |
| LED éteinte | Supply voltage input AC not present (Off) |
| Tension | 10 V (Test Level 3) |
| Commentaires | Criterion A |
| Déclassement | < 100 V AC ... 85 V AC (1 %/V) |
| Fonction | Visual operating state display |
| Position | 1.x |
| flexible | 0.2 mm² ... 2.5 mm² |
| Fréquence | 50 Hz |
| Temps de lever | typ. 100 ms (UOut= 10 % ... 90 %) |
| EN 61010-1 | II (≤ 3000 m) |
| EN 62477-1 | III (≤ 2000 m) |
| Efficacité | > 92.5 % (120 V AC) |
| Critère A | Normal operating behavior within the specified limits. |
| Critère B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Critère C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| chute de tension | 70 % |
| rigide (AWG) | 24 ... 14 (Cu) |
| Facteur Crest | typ. 1.78 |
| Entrée/Sortie | asymmetrical |
| Type de réseau | Star network |
| Type de produit | Power supply |
| Type de montage | DIN rail or direct mounting |
| Sans charge | yes |
| Identification | UL 1310 Class 2 Power Units |
| Courant d'appel | typ. 30 A (25 °C) |
| Émission de bruit | EN 55016 |
| Immunité au bruit | EN 61000-6-2:2005 |
| Famille de produits | STEP POWER |
| Heure de mise en marche | typ. 2 s |
| Texte supplémentaire | Class 3 |
| Gamme de fréquences | 0 kHz ... 2 kHz |
| Ondulation résiduelle | typ. 100 mVPP |
| Décharge dans l'air | 8 kV (Test Level 3) |
| Pas horizontal | 4 Div. (DIN 43880) |
| Matériau du boîtier | Plastic |
| Altitude maximale | ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m) |
| Nombre de phases | 1.00 |
| Marquage de position | 1.1, 1.2 (L), 1.3, 1.4 (N) |
| Classe de protection | II (in closed control cabinet) |
| Seuil de signal | > 0,9 x UN(UN= 24 V DC) (LED lights up green) |
| longueur de dénudage | 10 mm (rigid/flexible) |
| Méthode de connexion | Push-in connection |
| Sortie de contact | 6 kV (Test Level 3) |
| Écart de contrôle | < 0.5 % (Static load change 10 % ... 90 %) |
| fusible secteur de l'appareil | 4 A internal (device protection), slow-blow |
| Position de montage | horizontal DIN rail NS 35, EN 60715 |
| Nombre de périodes | 25 periods |
| Puissance de sortie (PN) | 90 W |
| Choc (opération) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
| circuit de protection | Transient surge protection; Varistor |
| Types de signalisation | LED DC OK – signal state operation (UN= 24 V DC, IOut= IN) |
| Consommation de courant | 1 A (100 V AC) |
| Degré de pollution | 2 |
| Dessin coté | |
| matériau de verrouillage au pied | Polyamid |
| Plage de tension d'entrée | 100 V AC ... 240 V AC -15 % ... +10 % |
| Protection contre les courts-circuits | yes |
| Force du champ d'essai | 10 V/m (Test Level 3) |
| Connexion en série | yes, for increased output voltage |
| Degré de protection | IP20 |
| Plage de fréquences (fN) | 50 Hz ... 60 Hz ±10 % |
| Temps de mise en mémoire tampon du réseau | typ. 25 ms (120 V AC) |
| Désignation standard | Electrical safety |
| Instructions de montage | alignable: 0 mm horizontally, 30 mm vertically |
| Émission d'interférences | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
| LED allumée (verte), courant continu OK | UOut>0.9 x UN(UN= 24 V DC) (on) |
| Directive Basse Tension | Conformance with Low Voltage Directive 2014/35/EC |
| Normes/réglementations | EN 61000-3-2 |
| Vibration (fonctionnement) | < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6) |
| Connexion en parallèle | yes, for increasing power and redundancy with diode |
| Tension de sortie nominale | 24 V DC |
| Courant de décharge vers PE | < 0.25 mA |
| Avec revêtement protecteur | PCB only |
| Émission de bruit conduit | EN 55016 |
| Normes/spécifications | IEC 61010-1 (SELV) |
| Protection par fusible intégrée | no |
| MTBF (IEC 61709, SN 29500) | > 2036000 h (25 °C) |
| résistance de la tension de rétroaction | ≤ 35 V DC |
| Courant de sortie nominal (IN) | 3.75 A |
| Perte de puissance charge nominale max. | < 5.7 W (230 V AC) |
| Compatibilité électromagnétique | Conformance with EMC Directive 2014/30/EU |
| Intégrale du courant d'appel (I2t) | typ. 0.35 A2s |
| Tension typique du réseau électrique national | 120 V AC |
| Type de tension d'alimentation | AC |
| Température ambiante (fonctionnement) | -10 °C ... 70 °C (Derating > 50°C: 2 %/K) |
| entrée/sortie de tension d'isolation | 4 kV AC (type test) |
| Distance d'installation droite/gauche | 0 mm / 0 mm |
| Distance d'installation haut/bas | 30 mm / 30 mm |
| Dissipation de puissance maximale à vide | < 0.21 W (230 V AC) |
| Dissipation de puissance minimale à vide | < 0.21 W (120 V AC) |
| directive relative à la protection de l'environnement | RoHS Directive 2011/65/EU |
| Indice d'inflammabilité selon la norme UL 94 | V0 (Housing, terminal blocks, base latches) |
| dissipation de puissance nominale minimale | < 7 W (120 V AC) |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Disjoncteur recommandé pour la protection de l'entrée | 6 A ... 16 A (Characteristics B, C, D, K) |
| flexible avec virole et gaine plastique | 0.2 mm² ... 1 mm² |
| Température ambiante (type de démarrage testé) | -40 °C |
| flexible avec virole sans gaine plastique | 0.5 mm² ... 1.5 mm² |
| Humidité relative maximale admissible (en fonctionnement) | ≤ 95 % (non-condensing) |
| Protection contre les surtensions en sortie (OVP) | < 35 V DC |
Spécifications techniques et données de performance
Guide d'installation et d'utilisation