| Paramètre | Valeur |
|---|---|
| 115 V AC ... 240 V AC ±10 % (UL) | |
| Couleur | red, yellow, green (multicolor LED) |
| Profondeur | 120 mm |
| E/S | asymmetrical |
| Saisir | asymmetrical 2 kV (Test Level 3) |
| Largeur | 35 mm |
| rigide | 0.2 mm² ... 4 mm² |
| Hauteur | 135 mm |
| Sortir | asymmetrical 2 kV (Test Level 3) |
| Signal | asymmetrical 1 kV (Test Level 3) |
| LED éteinte | Supply voltage input AC not present (Off) |
| Tension | 10 V (Test Level 3) |
| Commentaires | Criterion B |
| Déclassement | < 100 V AC (1 %/V) |
| Fonction | Visual operating state display |
| Position | 3.x |
| flexible | 0.2 mm² ... 2.5 mm² |
| Fréquence | 50 Hz |
| Temps de lever | ≤ 1 s (UOut= 10 % ... 90 %) |
| EN 61010-1 | III (≤ 2000 m) |
| Efficacité | typ. 93 % (120 V AC) |
| Critère A | Normal operating behavior within the specified limits. |
| Critère B | Temporary impairment to operational behavior that is corrected by the device itself. |
| Critère C | Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
| chute de tension | 70 % |
| rigide (AWG) | 24 ... 12 (Cu) |
| Facteur Crest | typ. 1.72 (120 V AC) |
| Version à capuche | Polycarbonate |
| Type de produit | Power supply |
| Type de montage | DIN rail mounting |
| Sans charge | yes |
| Identification | UL/C-UL Listed UL 61010-1 |
| Courant d'appel | < 33 A (25 °C) |
| Émission de bruit | EN 55016 |
| Immunité au bruit | Immunity in accordance with EN 61000-6-1 (residential), EN 61000-6-2 (industrial) |
| Famille de produits | TRIO POWER |
| Texte supplémentaire | Class 3 |
| EN 61010-2-201 | III (≤ 2000 m) |
| Gamme de fréquences | 0 kHz ... 2 kHz |
| Ondulation résiduelle | typ. 50 mVPP(with nominal values) |
| État de l'état | UOut> 21 V DC and IOutN (Contact closed) |
| Décharge dans l'air | 8 kV (Test Level 3) |
| Altitude maximale | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
| Nombre de phases | 1.00 |
| Marquage de position | 3.1 (13), 3.2 (14) |
| Classe de protection | I |
| longueur de dénudage | 10 mm (rigid/flexible) |
| Méthode de connexion | Push-in connection |
| Sortie de contact | 6 kV (Test Level 3) |
| Écart de contrôle | < 1 % (change in load, static 10 % ... 90 %) |
| fusible secteur de l'appareil | 6.3 A internal (device protection) |
| Position de montage | horizontal DIN rail NS 35, EN 60715 |
| Nombre de périodes | 25 periods |
| Puissance de sortie (PN) | 120 W |
| Choc (opération) | 18 ms, 30g, per spatial direction (IEC 60068-2-27) |
| Tension de commutation | max. 30 V DC (SELV) |
| circuit de protection | Transient protection; Varistor |
| Types de signalisation | LED DC OK – signal state operation (UN= 24 V DC, IOut= IN) |
| Consommation de courant | 1.3 A (100 V AC) |
| Degré de pollution | 2 |
| Plage de tension d'entrée | 100 V AC ... 240 V AC -15 % ... +10 % |
| Protection contre les courts-circuits | yes |
| Force du champ d'essai | 10 V/m (Test Level 3) |
| Connexion en série | yes, for increased output voltage (observe SELV limit) |
| Degré de protection | IP20 |
| Plage de fréquences (fN) | 50 Hz ... 60 Hz ±10 % |
| LED allumée (rouge), ISHORT | UOutOut > 0.9 x IN(On (red), ISHORT) |
| Temps de mise en mémoire tampon du réseau | typ. 28 ms (120 V AC) |
| Version avec élément latéral | Aluminum |
| Désignation standard | Safety of power supply units up to 1100 V (insulation distances) |
| Instructions de montage | alignable: 0 mm horizontally, 30 mm vertically |
| Émission d'interférences | Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial) |
| LED allumée (verte), courant continu OK | UOut> 21 V DC and IOutN (On (green), DC OK) |
| Directive Basse Tension | Conformance with Low Voltage Directive 2014/35/EC |
| Normes/réglementations | EN 61000-3-2 |
| Vibration (fonctionnement) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) |
| Connexion en parallèle | yes, for increased efficiency and redundancy |
| Tension de sortie nominale | 24 V DC |
| Facteur de puissance (cos phi) | 0.93 (230 V AC) |
| Courant de décharge vers PE | < 3.5 mA |
| Avec revêtement protecteur | No |
| Émission de bruit conduit | EN 55016 |
| Normes/spécifications | DIN EN 61558-2-16 |
| capacité de transport actuelle | max. 100 mA |
| Voyant LED allumé (rouge clignotant) OVP | UOUT> OVP (Over voltage protection) (On (flashing red)) |
| Contact de commutation (flottant) | OptoMOS |
| Boost dynamique (IDyn.Boost) | max. 7.5 A (5 s) |
| Protection par fusible intégrée | no |
| MTBF (IEC 61709, SN 29500) | > 3300000 h (25 °C) |
| Puissance de sortie (PDyn. Boost) | max. 180 W (5 s) |
| résistance de la tension de rétroaction | ≤ 35 V DC |
| LED allumée (jaune), IOut > 90 % | UOut> 21 V DC and IOut> 0.9 x IN(On (yellow), IOut> 90% ) |
| Plage de tension d'entrée nominale | 100 V AC ... 240 V AC |
| Courant de sortie nominal (IN) | 5 A |
| configuration du système d'approvisionnement | Star network (TN, TT, IT (PE)) |
| Perte de puissance charge nominale max. | < 6.51 W (230 V AC) |
| Compatibilité électromagnétique | Conformance with EMC Directive 2014/30/EU |
| Intégrale du courant d'appel (I2t) | < 0.55 A2s |
| Tension typique du réseau électrique national | 120 V AC |
| Type de tension d'alimentation | AC |
| Température ambiante (fonctionnement) | -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K) |
| entrée/sortie de tension d'isolation | 3 kV AC (type test) |
| Distance d'installation droite/gauche | 0 mm / 0 mm |
| Distance d'installation haut/bas | 50 mm / 50 mm |
| Dissipation de puissance maximale à vide | < 1.75 W (230 V AC) |
| Dissipation de puissance minimale à vide | < 2.14 W (120 V AC) |
| directive relative à la protection de l'environnement | RoHS Directive 2011/65/EU |
| Indice d'inflammabilité selon la norme UL 94 | V0 (Housing, terminal blocks) |
| dissipation de puissance nominale minimale | < 8.54 W (120 V AC) |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Disjoncteur recommandé pour la protection de l'entrée | 6 A ... 16 A (Characteristic B, C, D, K or comparable) |
| flexible avec virole et gaine plastique | 0.25 mm² ... 1.5 mm² |
| Température ambiante (type de démarrage testé) | -40 °C |
| Réglage de la plage de tension de sortie (USet) | 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted) |
| flexible avec virole sans gaine plastique | 0.25 mm² ... 2.5 mm² |
| Humidité relative maximale admissible (en fonctionnement) | ≤ 95 % (at 25 °C, non-condensing) |
| Protection contre les surtensions en sortie (OVP) | ≤ 35 V DC |
Spécifications techniques et données de performance