| Paramètre | Valeur |
|---|---|
| 2x 400V AC ... 500 V AC ±10% | |
| E/S | asymmetric |
| Sortie | asymmetric 2 kV (Test Severity 3) |
| Profondeur | 132 mm |
| Largeur | 60 mm |
| Rendement | Typ. 94.53% (3x 400 V AC) |
| rigide | 0.2 mm² ... 4 mm² |
| Couleur | Red, Yellow, Green (Multicolor LED) |
| Hauteur | 135 mm |
| Marqué | UL/C-UL Listed UL 61010-1 |
| Signal | asymmetric 1 kV (Test Severity 3) |
| LED éteinte | No supply voltage at Input AC (Off) |
| tension | 10 V (Test Severity 3) |
| Déclassement | 60 °C ... 70 °C |
| Position | 3.x |
| entrée | asymmetric 2 kV (Test Severity 3) |
| flexible | 0.2 mm² ... 2.5 mm² |
| fonction | Visual indication of operating status |
| fréquence | 50 Hz |
| EN 61010-1 | III (≤ 2000 m) |
| Temps d'ascension | ≤ 1 sec (UOut= 10% ... 90 %) |
| Critère A | Normal service behavior within the specified limits. |
| Critère B | Transient alteration of service behavior, which is corrected by the device itself. |
| Critère C | Temporary adverse effects on performance that are automatically corrected by the equipment or that can be reset by operating the control elements. |
| Observation | Criterion B |
| Longueur du pelage | 10 mm (rigid/flexible) |
| Rigide (AWG) | 24 ... 12 (Cu) |
| Facteur Crest | Typ. 1.51 (3x 400 V AC) |
| Type de produit | Power supply |
| Hauteur de fixation | ≤ 5000 m (> 2000 m, Derating: 10%/1000 m) |
| Statut Statut | UOut> 21 V DC & IOutN (Closed Contact) |
| Erreur de tension | 70 % |
| EN 61010-2-201 | III (≤ 2000 m) |
| Famille de produits | TRIO POWER |
| Texte supplémentaire | Class 3 |
| Type de connexion | Push-in connection |
| Gamme de fréquences | 0 kHz ... 2 kHz |
| Ondulation résiduelle | Typ. 15 mVPP(with nominal values) |
| Type de signalétique | LED DC OK - Operating Signal Status (UN= 24 V DC, IOut= IN) |
| Capacité actuelle | max. 100 mA |
| Nombre de phases | 3,00 |
| Indice de protection | IP20 |
| Règles/Dispositions | DIN EN 61558-2-16 |
| Type de montage | Rail mounting |
| Vidange constante | Yes |
| Écart de gradation | < 1% (static load change 10% ... 90 %) |
| Fusible d'entrée du module | 3.15 A internal (device protection) |
| Structure du réseau | Star Network (TN, TT, IT (PE)) |
| Nombre de périodes | 25 periods |
| Puissance de sortie (PN) | 480 W |
| Tension de commutation | MAX 30 V DC (SELV) |
| absorption du courant | 3x 0.77 A (3x 400 V AC) |
| Type de protection | I |
| Circuit de protection | Protection against transients; Varistor |
| Protection intégrée | No |
| Degré de pollution | 2 |
| Téléchargez notre formulaire de contact | 6 kV (Test Severity 3) |
| Plage de tension d'entrée | 3x 400V AC ... 500 V AC -20% ... +10% |
| Identification des poteaux | 3.1 (13), 3.2 (14) |
| Accidents (en service) | 18 ms, 30g, for each local address (IEC 60068-2-27) |
| Exécution du cap | Polycarbonate |
| Plage de fréquences (fN) | 50 Hz ... 60 Hz ±10% |
| LED allumée (rouge), ISHORT | UOutOut > 0.9 x IN(on (red), ISHORTS) |
| Intensité du champ de test | 10 V/m (Test Severity 3) |
| Émission d'interférences | Interference emission in accordance with EN 61000-6-3 (residential and commercial areas) and EN 61000-6-4 (industrial areas) |
| LED allumée (verte), courant continu OK | UOut> 21 V DC & IOutN (on (green), DC OK) |
| Directive Basse Tension | Compliance with the Low Voltage Directive 2014/35/EU |
| Position de montage | Horizontal rail NS 35, EN 60715 |
| Rejet dans l'air | 8 kV (Test Severity 3) |
| Coupure de courant supplémentaire | < 13 A (25 °C) |
| Tension de sortie nominale | 24 V DC |
| Facteur de puissance (cos phi) | 0.93 (3x 480 V AC) |
| Vibrations (en service) | 10 Hz ... 50 Hz, amplitude ±0.2 mm (IEC 60068-2-6) |
| Résistance aux interférences | Immunity to interference according to EN 61000-6-1 (domestic use), EN 61000-6-2 (industrial use) |
| résistance aux courts-circuits | Yes |
| Dénomination de l'étalon | Safety of power supplies up to 1100 V (isolation distances) |
| Résistance à la recirculation | ≤ 35 V DC |
| Normes/Spécifications | EN 61000-3-2 |
| Courant de shunt à la terre (PE) | < 3.5 mA |
| Instructions d'installation | Alignable: horizontal 0 mm, vertical 30 mm |
| Voyant LED allumé (clignotant rouge) OVP | UOUT> OVP (Over voltage protection) (on (flashing red)) |
| Distance de montage vers le haut/vers le bas | 50 mm / 50 mm |
| Courant de sortie nominal (IN) | 20 A |
| Boost dynamique (IDyn.Boost) | max. 30 A (5 sec) |
| MTBF (IEC 61709, SN 29500) | > 1100000 h (25 °C) |
| Puissance de sortie (PDyn. Boost) | max. 720 W (5 sec) |
| LED allumée (jaune), IOut > 90 % | UOut> 21 V DC & IOut> 0.9 x IN(on (yellow), IOut> 90%) |
| Plage de tension d'entrée nominale | 3x 400V AC ... 500 V AC |
| Émissions parasites rayonnées | EN 55016 |
| Type de tension d'alimentation | AC |
| Connexion parallèle possible | Yes, to increase power and redundancy with diode |
| Distance de montage droite/gauche | 0 mm / 0 mm |
| Tension typique du réseau électrique du pays | 3x 400V AC |
| Température ambiante (Service) | -25 °C ... 70 °C (> 60 °C Derating: 2.5%/K) |
| Compatibilité électromagnétique | Compliance with EMC Directive 2014/30/EU |
| Intégrale du courant d'appel (I2t) | < 0.33 A2s |
| Temps de pontage en cas de défaillance du réseau | Typ. 28 ms (3x 400 V AC) |
| Protection contre les surtensions de sortie (OVP) | ≤ 35 V DC |
| Exécution des éléments secondaires | aluminium |
| Dissipation de charge nominale maximale | < 27.35 W (3x 480 V AC) |
| Tension d'isolation d'entrée/sortie | 4 kV AC (type test) |
| Dissipation maximale en circuit ouvert | < 3.1 W (3x 480 V AC) |
| Possibilité de connexion en série | yes, to increase the tension (observe the SELV limit) |
| Émission d'interférences conduites | EN 55016 |
| Directive relative à la protection de l'environnement | RoHS Directive 2011/65/EU |
| Embout souple avec bordure en plastique | 0.25 mm² ... 1.5 mm² |
| Classe d'inflammabilité selon la norme UL 94 | V0 (Housing, terminals) |
| Contact commuté (sans potentiel) | OptoMOS |
| Plage de réglage de la tension de sortie (Uset) | 24 V DC ... 28 V DC (> 24 V DC, limited by power constant) |
| Puissance dissipée à la charge nominale minimale | < 26.08 W (3x 400 V AC) |
| Température ambiante (stockage/transport) | -40 °C ... 85 °C |
| Embout souple sans manchon en plastique | 0.25 mm² ... 2.5 mm² |
| Humidité de l'air maximale admissible (service) | ≤ 95% (at 25°C, non-condensing) |
| Puissance minimale dissipée en mode vide | < 3 W (3x 400 V AC) |
| Température ambiante (modèle testé au démarrage) | -40 °C |
| Choisir le bon fusible pour la protection contre les infiltrations | 3x 6 A ... 16 A (Characteristic B, C, D, K or comparable) |